ICSA-22-104-06

icsaUScisa_csaf_ot

Siemens PROFINET Stack Integrated on Interniche Stack

Advisory ansehen veröffentlicht 2022-04-12

The PROFINET (PNIO) stack, when integrated with the Interniche IP stack, contains a vulnerability that could allow an attacker to cause a denial of service condition on affected industrial products. Siemens has released new versions for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where fixes are not, or not yet available.

01

beschreibt (1)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2022-25622UShigh7.5—
The PROFINET (PNIO) stack, when integrated with the Interniche IP stack, improperly handles internal resources for TCP segments where the minimum TCP-Header length is less than def…
02

Referenzen

Externe Belege — Patches, Meldungen, Analysen.

03

Behebungen (164)

  • Mitigation SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • Mitigation SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • Mitigation SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • Mitigation SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC CFU DIQ (6ES7655-5PX31-1XX0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC CFU PA (6ES7655-5PX11-0XX0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET200ecoPN, AI 8xRTD/TC, M12-L (6ES7144-6JF00-0BB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET200ecoPN, CM 4x IO-Link, M12-L (6ES7148-6JE00-0BB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET200ecoPN, CM 8x IO-Link, M12-L (6ES7148-6JG00-0BB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET200ecoPN, CM 8x IO-Link, M12-L (6ES7148-6JJ00-0BB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET200ecoPN, DI 16x24VDC, M12-L (6ES7141-6BH00-0BB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET200ecoPN, DI 8x24VDC, M12-L (6ES7141-6BG00-0BB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET200ecoPN, DIQ 16x24VDC/2A, M12-L (6ES7143-6BH00-0BB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET200ecoPN, DQ 8x24VDC/0,5A, M12-L (6ES7142-6BG00-0BB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC ET200ecoPN, DQ 8x24VDC/2A, M12-L (6ES7142-6BR00-0BB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-410 V10 CPU family (incl. SIPLUS variants)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC S7-410 V8 CPU family (incl. SIPLUS variants)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC TDC CP51M1

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC TDC CPU555

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSINAMICS DCM

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSINAMICS G110M

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSINAMICS G115D

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSINAMICS G120 (incl. SIPLUS variants)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSINAMICS G130

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSINAMICS G150

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSINAMICS S110

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSINAMICS S120 (incl. SIPLUS variants)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSINAMICS S150

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSINAMICS S210 (6SL5...)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSINAMICS V90

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS HCS4200 CIM4210 (6BK1942-1AA00-0AA0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS HCS4200 CIM4210C (6BK1942-1AA00-0AA1)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS HCS4300 CIM4310 (6BK1943-1AA00-0AA0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • MitigationSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)

    Limit access to port 102/tcp to trusted users and systems only

  • Kein Fix geplant SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)

    Currently no fix is planned

  • Kein Fix geplant SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)

    Currently no fix is planned

  • Kein Fix geplant SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)

    Currently no fix is planned

  • Kein Fix geplant SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0)

    Currently no fix is planned

  • Kein Fix geplantSINAMICS S110

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS HCS4200 CIM4210 (6BK1942-1AA00-0AA0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS HCS4200 CIM4210C (6BK1942-1AA00-0AA1)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS HCS4300 CIM4310 (6BK1943-1AA00-0AA0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)

    Currently no fix is planned

  • BehobenSIMATIC CFU DIQ (6ES7655-5PX31-1XX0)

    Update to V2.0.0 or later version

  • BehobenSIMATIC CFU PA (6ES7655-5PX11-0XX0)

    Update to V2.0.0 or later version

  • BehobenSIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47353723/
  • BehobenSIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47354354/
  • BehobenSIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47354502/
  • BehobenSIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47354578/
  • BehobenSIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/62612377/
  • BehobenSIMATIC ET200ecoPN, AI 8xRTD/TC, M12-L (6ES7144-6JF00-0BB0)

    Update to V5.1.2 or later version

  • BehobenSIMATIC ET200ecoPN, CM 4x IO-Link, M12-L (6ES7148-6JE00-0BB0)

    Update to V5.1.2 or later version

  • BehobenSIMATIC ET200ecoPN, CM 8x IO-Link, M12-L (6ES7148-6JG00-0BB0)

    Update to V5.1.2 or later version

  • BehobenSIMATIC ET200ecoPN, CM 8x IO-Link, M12-L (6ES7148-6JJ00-0BB0)

    Update to V5.1.2 or later version

  • BehobenSIMATIC ET200ecoPN, DI 16x24VDC, M12-L (6ES7141-6BH00-0BB0)

    Update to V5.1.2 or later version

  • BehobenSIMATIC ET200ecoPN, DI 8x24VDC, M12-L (6ES7141-6BG00-0BB0)

    Update to V5.1.2 or later version

  • BehobenSIMATIC ET200ecoPN, DIQ 16x24VDC/2A, M12-L (6ES7143-6BH00-0BB0)

    Update to V5.1.3 or later version

  • BehobenSIMATIC ET200ecoPN, DQ 8x24VDC/0,5A, M12-L (6ES7142-6BG00-0BB0)

    Update to V5.1.2 or later version

  • BehobenSIMATIC ET200ecoPN, DQ 8x24VDC/2A, M12-L (6ES7142-6BR00-0BB0)

    Update to V5.1.2 or later version

  • BehobenSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)

    Update to V2.0.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109478459/
  • BehobenSIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0)

    Update to V3.3.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/51466769/
  • BehobenSIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40360647/
  • BehobenSIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40944925/
  • BehobenSIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/85049260/
  • BehobenSIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40362228/
  • BehobenSIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40945128/
  • BehobenSIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/85059804/
  • BehobenSIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/85063017/
  • BehobenSIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/44442927/
  • BehobenSIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/44443101/
  • BehobenSIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants)

    Update to V6.0.10 or later version

  • BehobenSIMATIC S7-410 V10 CPU family (incl. SIPLUS variants)

    Update to V10.1.1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109773044/
  • BehobenSIMATIC S7-410 V8 CPU family (incl. SIPLUS variants)

    Update to V8.2.3 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109476571/
  • BehobenSIMATIC TDC CP51M1

    Update to V1.1.10 or later version

    https://support.industry.siemens.com/cs/ww/en/view/27049282/
  • BehobenSIMATIC TDC CPU555

    Update to V1.2.1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109740119/
  • BehobenSINAMICS DCM

    Update to V1.5 SP1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/44029688/
  • BehobenSINAMICS G110M

    Update to V4.7.14 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109817231/
  • BehobenSINAMICS G115D

    Update to V4.7.14 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109817231/
  • BehobenSINAMICS G120 (incl. SIPLUS variants)

    Update to V4.7 SP14 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109817231/
  • BehobenSINAMICS G130

    Update to V5.2.3.13 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109764679/
  • BehobenSINAMICS G150

    Update to V5.2.3.13 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109764679/
  • BehobenSINAMICS S120 (incl. SIPLUS variants)

    Update to V5.2 SP3 HF13 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109780844/
  • BehobenSINAMICS S150

    Update to V5.2.3.13 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109764679/
  • BehobenSINAMICS S210 (6SL5...)

    Update to V5.2 SP3 HF18 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109945645/
  • BehobenSINAMICS V90

    Update to V1.04.04 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109746210/
  • BehobenSIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47353723/
  • BehobenSIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47354354/
  • BehobenSIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0)

    Update to V3.3.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/51466769/
  • BehobenSIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40360647/
  • BehobenSIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40944925/
  • BehobenSIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40362228/
  • BehobenSIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0)

    Update to V3.2.19 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40945128/