ICSA-25-016-08

icsaUScisa_csaf_ot

Schneider Electric Data Center Expert

Advisory ansehen veröffentlicht 2024-10-08

Schneider Electric is aware of a vulnerability in its Data Center Expert product. The Data Center Expert product is a scalable monitoring software that collects, organizes, and distributes critical device information providing a comprehensive view of equipment. Failure to apply the fix provided below may risk information disclosure, which could result in access to private data.

01

beschreibt (2)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2024-8531US——
CWE-347: Improper Verification of Cryptographic Signature vulnerability exists that could compromise the Data Center Expert software when an upgrade bundle is manipulated to includ…
CVE-2024-8530US—OT erhöht—
CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause exposure of private data when an already generated “logcaptures” archive is accessed dir…
02

Referenzen

Externe Belege — Patches, Meldungen, Analysen.

03

Behebungen (4)

  • MitigationData Center Expert

    Ensure that the principals of least privilege are being followed so that only those with need have account access and that the level of their respective account authorization aligns with their role, including Privileged Accounts as described in the Data Center Expert Security Handbook. • Verify SHA1 checksums of upgrade bundles prior to executing upgrades as described in the Upgrades section of the Data Center Expert Security Handbook.. • Delete any existing “logcapture” archives present on the system and do not create any new “logcapture” archives. Existing archives can be deleted from the https://server_ip/capturelogs web page after authenticating.

  • MitigationData Center Expert

    Ensure that the principals of least privilege are being followed so that only those with need have account access and that the level of their respective account authorization aligns with their role, including Privileged Accounts as described in the Data Center Expert Security Handbook. • Verify SHA1 checksums of upgrade bundles prior to executing upgrades as described in the Upgrades section of the Data Center Expert Security Handbook.. • Delete any existing “logcapture” archives present on the system and do not create any new “logcapture” archives. Existing archives can be deleted from the https://server_ip/capturelogs web page after authenticating.

  • BehobenData Center Expert

    Version 8.2 of EcoStruxure™ IT Data Center Expert includes fixes for these vulnerabilities and is available upon request from Schneider Electric’s Customer Care Center.

  • BehobenData Center Expert

    Version 8.2 of EcoStruxure™ IT Data Center Expert includes fixes for these vulnerabilities and is available upon request from Schneider Electric’s Customer Care Center.