Rockwell Automation Stratix 5400/5410/5700 and ArmorStratix 5700
Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to cause a memory leak on an affected device, which may cause the device to reload.
beschreibt (1)
Zugehörige CVEs.
| ID | Schweregrad | ausnutzbar | ||
|---|---|---|---|---|
| CVE-2018-15377US | high8.6 | — | ||
A vulnerability in the Cisco Network Plug and Play agent, also referred to as the Cisco Open Plug-n-Play agent, of Cisco IOS Software and Cisco IOS XE Software could allow an unaut… | ||||
Referenzen
Externe Belege — Patches, Meldungen, Analysen.
Behebungen (4)
- MitigationAllen-Bradley ArmorStratix 5700
Block all traffic to EtherNet/IP, or other CIP protocol-based devices, from outside the manufacturing zone by blocking or restricting access to TCP and UDP Port 2222 and Port 44818 using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation Products, see Knowledgebase Article ID 898270.
- MitigationAllen-Bradley Stratix 5400
Block all traffic to EtherNet/IP, or other CIP protocol-based devices, from outside the manufacturing zone by blocking or restricting access to TCP and UDP Port 2222 and Port 44818 using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation Products, see Knowledgebase Article ID 898270.
- MitigationAllen-Bradley Stratix 5410
Block all traffic to EtherNet/IP, or other CIP protocol-based devices, from outside the manufacturing zone by blocking or restricting access to TCP and UDP Port 2222 and Port 44818 using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation Products, see Knowledgebase Article ID 898270.
- MitigationAllen-Bradley Stratix 5700
Block all traffic to EtherNet/IP, or other CIP protocol-based devices, from outside the manufacturing zone by blocking or restricting access to TCP and UDP Port 2222 and Port 44818 using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation Products, see Knowledgebase Article ID 898270.