ICSA-18-324-02

icsaUScisa_csaf_ot

Schneider Electric Modicon M221

Advisory ansehen veröffentlicht 2018-11-20

Successful exploitation of this vulnerability could cause a change of IPv4 configuration (IP address, mask, and gateway) when remotely connected to the device.

01

beschreibt (1)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2018-7798UShigh8.2OT erhöht—
A Insufficient Verification of Data Authenticity (CWE-345) vulnerability exists in the Modicon M221, all versions, which could cause a change of IPv4 configuration (IP address, mas…
02

Referenzen

Externe Belege — Patches, Meldungen, Analysen.

03

Behebungen (2)

  • MitigationModicon M221

    All controllers should reside in locked cabinets and never be left in the “Program” mode.

  • BehobenModicon M221

    Within the Modicon M221 application, users should disable all unused protocols, especially programming protocol, as described in section “Configuring Ethernet Network” of SoMachine Basic online help. This will prevent remote programming of the M221 PLC.

scry

Advisories wie diese benennen die exponierten Produkte, die Angreifer auf Ihrer Angriffsfläche ins Visier nehmen. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan