Schneider Electric Modicon M221
Successful exploitation of this vulnerability could cause a change of IPv4 configuration (IP address, mask, and gateway) when remotely connected to the device.
beschreibt (1)
Zugehörige CVEs.
| ID | Schweregrad | ausnutzbar | ||
|---|---|---|---|---|
| CVE-2018-7798US | high8.2OT erhöht | — | ||
A Insufficient Verification of Data Authenticity (CWE-345) vulnerability exists in the Modicon M221, all versions, which could cause a change of IPv4 configuration (IP address, mas… | ||||
Referenzen
Externe Belege — Patches, Meldungen, Analysen.
Behebungen (2)
- MitigationModicon M221
All controllers should reside in locked cabinets and never be left in the “Program” mode.
- BehobenModicon M221
Within the Modicon M221 application, users should disable all unused protocols, especially programming protocol, as described in section “Configuring Ethernet Network” of SoMachine Basic online help. This will prevent remote programming of the M221 PLC.