ICSA-17-187-03F

icsaUScisa_csaf_ot

ICSA-17-187-03F Siemens SIPROTEC 4 and SIPROTEC Compact (Update F)

Advisory ansehen veröffentlicht 2017-07-04

CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.

01

beschreibt (6)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2016-7114UShigh8.8OT erhöht—
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All…
CVE-2016-7113UShigh7.5—
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All…
CVE-2016-7112UScritical9.8OT erhöht—
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All…
CVE-2016-4785USmedium5.3OT erhöht—
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All…
CVE-2016-4784USmedium5.3OT erhöht—
A vulnerability has been identified in firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All…
CVE-2015-5374UShigh7.8Exploit
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All…
02

Referenzen

Externe Belege — Patches, Meldungen, Analysen.

03

Behebungen (80)

  • MitigationEN100 Ethernet module included in SIPROTEC Merging Unit 6MU80

    Install V1.02.02 - Download: Please contact the Siemens hotline at support.energy@siemens.com

  • MitigationEN100 Ethernet module included in SIPROTEC Merging Unit 6MU80

    Install V1.02.02 - Download: Please contact the Siemens hotline at support.energy@siemens.com

  • MitigationEN100 Ethernet module included in SIPROTEC Merging Unit 6MU80

    Install V1.02.02 - Download: Please contact the Siemens hotline at support.energy@siemens.com

  • MitigationEN100 Ethernet module included in SIPROTEC Merging Unit 6MU80

    Install V1.02.02 - Download: Please contact the Siemens hotline at support.energy@siemens.com

  • MitigationEN100 Ethernet module included in SIPROTEC Merging Unit 6MU80

    Install V1.02.02 - Download: Please contact the Siemens hotline at support.energy@siemens.com

  • MitigationEN100 Ethernet module included in SIPROTEC Merging Unit 6MU80

    Install V1.02.02 - Download: Please contact the Siemens hotline at support.energy@siemens.com

  • MitigationFirmware variant DNP3 TCP for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant DNP3 TCP for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant DNP3 TCP for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant DNP3 TCP for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant DNP3 TCP for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant DNP3 TCP for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant IEC 104 for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant IEC 104 for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant IEC 104 for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant IEC 104 for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant IEC 104 for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant IEC 104 for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant Modbus TCP for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant Modbus TCP for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant Modbus TCP for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant Modbus TCP for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant Modbus TCP for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant Modbus TCP for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant PROFINET IO for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant PROFINET IO for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant PROFINET IO for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant PROFINET IO for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant PROFINET IO for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationFirmware variant PROFINET IO for EN100 Ethernet module

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SD686

    Install V 4.03 - Download: http://www.siemensenergysector.com/ProductRelatedDown.aspx?ProductId=64

  • MitigationSIPROTEC 7SD686

    Install V4.05 - Download: http://www.siemensenergysector.com/ProductRelatedDown.aspx?ProductId=64

  • MitigationSIPROTEC 7SD686

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SD686

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SD686

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SD686

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SJ66

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SJ66

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SJ66

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SJ66

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SJ66

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SJ66

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SJ686

    Install V 4.83 - Download: http://www.siemensenergysector.com/ProductRelatedDown.aspx?ProductId=51

  • MitigationSIPROTEC 7SJ686

    Install V 4.87 - Download: http://www.siemensenergysector.com/ProductRelatedDown.aspx?ProductId=51

  • MitigationSIPROTEC 7SJ686

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SJ686

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SJ686

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7SJ686

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7UT686

    Install V 4.01 - Download: http://www.siemensenergysector.com/ProductRelatedDown.aspx?ProductId=68

  • MitigationSIPROTEC 7UT686

    Install V4.02 - Download: http://www.siemensenergysector.com/ProductRelatedDown.aspx?ProductId=68

  • MitigationSIPROTEC 7UT686

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7UT686

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7UT686

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • MitigationSIPROTEC 7UT686

    Siemens has identified the following specific workarounds and mitigations thatcustomers can apply to reduce the risk: Restrict network access to port 80/TCP and port 50000/UDP

  • BehobenFirmware variant DNP3 TCP for EN100 Ethernet module

    Install V1.03 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant DNP3 TCP for EN100 Ethernet module

    Install V1.03 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant DNP3 TCP for EN100 Ethernet module

    Install V1.03 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant DNP3 TCP for EN100 Ethernet module

    Install V1.03 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant DNP3 TCP for EN100 Ethernet module

    Install V1.03 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant DNP3 TCP for EN100 Ethernet module

    Install V1.03 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant IEC 104 for EN100 Ethernet module

    Install V1.21 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant IEC 104 for EN100 Ethernet module

    Install V1.21 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant IEC 104 for EN100 Ethernet module

    Install V1.21 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant IEC 104 for EN100 Ethernet module

    Install V1.21 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant IEC 104 for EN100 Ethernet module

    Install V1.21 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant IEC 104 for EN100 Ethernet module

    Install V1.21 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant Modbus TCP for EN100 Ethernet module

    Install V1.11.00 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant Modbus TCP for EN100 Ethernet module

    Install V1.11.00 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant Modbus TCP for EN100 Ethernet module

    Install V1.11.00 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant Modbus TCP for EN100 Ethernet module

    Install V1.11.00 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant Modbus TCP for EN100 Ethernet module

    Install V1.11.00 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant Modbus TCP for EN100 Ethernet module

    Install V1.11.00 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant PROFINET IO for EN100 Ethernet module

    Install V1.04.01 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant PROFINET IO for EN100 Ethernet module

    Install V1.04.01 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant PROFINET IO for EN100 Ethernet module

    Install V1.04.01 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant PROFINET IO for EN100 Ethernet module

    Install V1.04.01 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant PROFINET IO for EN100 Ethernet module

    Install V1.04.01 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenFirmware variant PROFINET IO for EN100 Ethernet module

    Install V1.04.01 - Download: https://support.industry.siemens.com/cs/us/en/view/109745821

    https://support.industry.siemens.com/cs/us/en/view/109745821
  • BehobenSIPROTEC 7SJ66

    Install V 4.20 - Download: https://support.industry.siemens.com/cs/gb/en/view/109743555

    https://support.industry.siemens.com/cs/gb/en/view/109743555
  • BehobenSIPROTEC 7SJ66

    Install V 4.30 - Download: https://support.industry.siemens.com/cs/us/en/view/109743555

    https://support.industry.siemens.com/cs/us/en/view/109743555