ABB MV Drives Affected by CODESYS RTS (Runtime System) Vulnerabilities
Multiple vulnerabilities regarding the CODESYS Runtime System from CODESYS Group have been publicly reported. CODESYS Runtime System v.3.5.15.0 is utilized in the firmware of ABB MV ACS6080 and ACS5000 drives to provide IEC 61131 programming capabilities. These vulnerabilities could lead to out-of-bound memory access. A successful exploit may result in a denial-of-service condition or arbitrary code execution. Firmware updates are available to address the vulnerabilities in products listed as affected in this advisory.
describes (15)
Related CVEs.
| ID | severity | exploitable | ||
|---|---|---|---|---|
| CVE-2022-4046US | — | — | ||
In CODESYS Control in multiple versions a improper restriction of operations within the bounds of a memory buffer allow an remote attacker with user privileges to gain full access… | ||||
| CVE-2023-37559US | — | — | ||
After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted network communication requests with inconsistent content can cause the… | ||||
| CVE-2023-37558US | — | — | ||
After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted network communication requests with inconsistent content can cause the… | ||||
| CVE-2023-37557US | — | — | ||
After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted remote communication requests can cause the CmpAppBP component to over… | ||||
| CVE-2023-37556US | — | — | ||
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause th… | ||||
| CVE-2023-37555US | — | — | ||
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause th… | ||||
| CVE-2023-37554US | — | — | ||
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause th… | ||||
| CVE-2023-37553US | — | — | ||
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause th… | ||||
| CVE-2023-37552US | medium6.5 | — | ||
In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause th… | ||||
| CVE-2023-37550US | — | — | ||
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause th… | ||||
| CVE-2023-37549US | — | — | ||
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause th… | ||||
| CVE-2023-37548US | — | — | ||
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause th… | ||||
| CVE-2023-37547US | — | — | ||
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause th… | ||||
| CVE-2023-37546US | — | — | ||
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause th… | ||||
| CVE-2023-37545US | — | — | ||
In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with inconsistent content can cause th… | ||||
references
External citations — patches, advisories, analysis.
- CODESYS Security Advisory 2023-04
- CODESYS Security Advisory 2023-05
- ACS5000 - ABB medium voltage AC drives medium voltage AC drives | ABB
- ACS6080 - ABB medium voltage AC drives medium voltage AC drives | ABB
- What is a variable speed drive | Drives | ABB
- ABB CYBERSECURITY ADVISORY - CSAF versionself
- Protecting operations through cyber security: ABB Drives solutions
- ABB CYBERSECURITY ADVISORY - PDF versionself
remediations (45)
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS5000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6000
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.
- FixedACS6080
ABB recommends that customers apply a firmware update as soon as possible to the latest firmware, i.e. LAAAB v. 5.07 and higher, for the affected products. ABB has addressed the CODESYS Runtime System vulnerabilities by disabling the IEC online programming communication by default. As a result, CODESYS communication between affected products and the ABB Automation Builder or ABB Drive Application Builder tools is disabled. It should be noted that the CODESYS application continues to run on the Drive and if it is necessary to establish communication with CODESYS RTS, for example to debug the CODESYS application, this is possible through the drive parameter configuration. Open the user lock via the "96.02 Pass code" parameter and make sure that bit 9 "Enable online IEC programming" is set to TRUE in the "96.102 User lock functionality" parameter. IMPORTANT: After this task, be sure to disable CODESYS communication by setting the bit back to FALSE. A future firmware update is planned to update the CODESYS RTS library, which will further strengthen defenses for the vulnerabilities mentioned above. For situations where firmware update is not feasible, please refer to “Workarounds” section.