SSA-473245

csafDEsiemens_psirt

SSA-473245: Denial of Service Vulnerability in Profinet Devices

view advisory published 2019-10-08

A vulnerability in affected devices could allow an attacker to perform a denial of service attack if a large amount of specially crafted UDP packets are sent to the device. Siemens has released new versions for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where fixes are not, or not yet available.

01

describes (1)

Related CVEs.

IDseverity exploitable
CVE-2019-10936USmedium5.0—
Affected devices improperly handle large amounts of specially crafted UDP packets. This could allow an unauthenticated remote attacker to trigger a denial of service condition.
02

references

External citations — patches, advisories, analysis.

03

remediations (240)

  • Mitigation SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)

    Restrict network access to affected devices

  • Mitigation SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)

    Restrict network access to affected devices

  • Mitigation SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)

    Restrict network access to affected devices

  • Mitigation SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)

    Restrict network access to affected devices

  • MitigationDevelopment/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller

    Restrict network access to affected devices

  • MitigationDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200

    Restrict network access to affected devices

  • MitigationDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200P

    Restrict network access to affected devices

  • MitigationSIMATIC CFU PA (6ES7655-5PX11-0XX0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200M (incl. SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200MP IM 155-5 PN BA (6ES7155-5AA00-0AA0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200MP IM 155-5 PN ST (6ES7155-5AA00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200MP IM 155-5 PN ST (6ES7155-5AA01-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200SP IM 155-6 PN BA (6ES7155-6AR00-0AN0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200SP IM 155-6 PN HS (6ES7155-6AU00-0DN0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU00-0BN0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU01-0BN0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA00-0BN0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA01-0BN0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200pro IM 154-3 PN HF (6ES7154-3AB00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200pro IM 154-4 PN HF (6ES7154-4AB10-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200S (incl. SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN, 16DI, DC24V, 8xM12 (6ES7141-6BH00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN, 4AO U/I 4xM12 (6ES7145-6HD00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN, 8DI, DC24V, 4xM12 (6ES7141-6BF00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12 (6ES7142-6BF50-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC HMI Comfort Outdoor Panels (incl. SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSIMATIC HMI Comfort Panels (incl. SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSIMATIC HMI KTP Mobile Panels

    Restrict network access to affected devices

  • MitigationSIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0)

    Restrict network access to affected devices

  • MitigationSIMATIC PROFINET Driver

    Restrict network access to affected devices

  • MitigationSIMATIC S7-1200 CPU family (incl. SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-1500 Software Controller

    Restrict network access to affected devices

  • MitigationSIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSIMATIC S7-410 V8 CPU family (incl. SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSIMATIC TDC CP51M1

    Restrict network access to affected devices

  • MitigationSIMATIC TDC CPU555

    Restrict network access to affected devices

  • MitigationSIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0)

    Restrict network access to affected devices

  • MitigationSIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0)

    Restrict network access to affected devices

  • MitigationSINAMICS DCM

    Restrict network access to affected devices

  • MitigationSINAMICS DCP

    Restrict network access to affected devices

  • MitigationSINAMICS G110M V4.7 PN Control Unit

    Restrict network access to affected devices

  • MitigationSINAMICS G120 V4.7 PN Control Unit (incl. SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSINAMICS G130 V4.7 Control Unit

    Restrict network access to affected devices

  • MitigationSINAMICS G150 Control Unit

    Restrict network access to affected devices

  • MitigationSINAMICS GH150 V4.7 Control Unit

    Restrict network access to affected devices

  • MitigationSINAMICS GL150 V4.7 Control Unit

    Restrict network access to affected devices

  • MitigationSINAMICS GM150 V4.7 Control Unit

    Restrict network access to affected devices

  • MitigationSINAMICS S110 Control Unit

    Restrict network access to affected devices

  • MitigationSINAMICS S120 V4.7 Control Unit (incl. SIPLUS variants)

    Restrict network access to affected devices

  • MitigationSINAMICS S150 Control Unit

    Restrict network access to affected devices

  • MitigationSINAMICS SL150 V4.7 Control Unit

    Restrict network access to affected devices

  • MitigationSINAMICS SM120 V4.7 Control Unit

    Restrict network access to affected devices

  • MitigationSINUMERIK 828D

    Restrict network access to affected devices

  • MitigationSINUMERIK 840D sl

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200MP IM 155-5 PN ST (6AG1155-5AA00-7AB0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200MP IM 155-5 PN ST (6AG1155-5AA01-7AB0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200MP IM 155-5 PN ST TX RAIL (6AG2155-5AA00-4AB0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200MP IM 155-5 PN ST TX RAIL (6AG2155-5AA01-4AB0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU00-7BN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU01-7BN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA00-7BN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA01-7BN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA00-4BN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA01-4BN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU00-4BN0)

    Restrict network access to affected devices

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU01-4BN0)

    Restrict network access to affected devices

  • MitigationSIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0)

    Restrict network access to affected devices

  • MitigationSIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0)

    Restrict network access to affected devices

  • MitigationSIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0)

    Restrict network access to affected devices

  • MitigationSIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0)

    Restrict network access to affected devices

  • MitigationSIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0)

    Restrict network access to affected devices

  • MitigationSIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0)

    Restrict network access to affected devices

  • MitigationSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)

    Restrict network access to affected devices

  • MitigationSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)

    Restrict network access to affected devices

  • No fix plannedDevelopment/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller

    Currently no fix is planned

  • No fix plannedDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200

    Currently no fix is planned

  • No fix plannedSIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET 200M (incl. SIPLUS variants)

    Currently no fix is planned

  • No fix plannedSIMATIC ET 200MP IM 155-5 PN ST (6ES7155-5AA00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET 200MP IM 155-5 PN ST (6ES7155-5AA01-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET 200SP IM 155-6 PN BA (6ES7155-6AR00-0AN0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU00-0BN0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU01-0BN0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA00-0BN0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA01-0BN0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET 200pro IM 154-3 PN HF (6ES7154-3AB00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET 200pro IM 154-4 PN HF (6ES7154-4AB10-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200S (incl. SIPLUS variants)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN, 16DI, DC24V, 8xM12 (6ES7141-6BH00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN, 4AO U/I 4xM12 (6ES7145-6HD00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN, 8DI, DC24V, 4xM12 (6ES7141-6BF00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12 (6ES7142-6BF50-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0)

    Currently no fix is planned

  • No fix plannedSIMATIC HMI Comfort Outdoor Panels (incl. SIPLUS variants)

    Currently no fix is planned

  • No fix plannedSIMATIC HMI Comfort Panels (incl. SIPLUS variants)

    Currently no fix is planned

  • No fix plannedSIMATIC HMI KTP Mobile Panels

    Currently no fix is planned

  • No fix plannedSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)

    Currently no fix is planned

  • No fix plannedSIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)

    Currently no fix is planned

  • No fix plannedSINAMICS S110 Control Unit

    Currently no fix is planned

  • No fix plannedSINAMICS SM120 V4.7 Control Unit

    Currently no fix is planned

  • No fix plannedSIPLUS ET 200MP IM 155-5 PN ST (6AG1155-5AA00-7AB0)

    Currently no fix is planned

  • No fix plannedSIPLUS ET 200MP IM 155-5 PN ST (6AG1155-5AA01-7AB0)

    Currently no fix is planned

  • No fix plannedSIPLUS ET 200MP IM 155-5 PN ST TX RAIL (6AG2155-5AA00-4AB0)

    Currently no fix is planned

  • No fix plannedSIPLUS ET 200MP IM 155-5 PN ST TX RAIL (6AG2155-5AA01-4AB0)

    Currently no fix is planned

  • No fix plannedSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU00-7BN0)

    Currently no fix is planned

  • No fix plannedSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU01-7BN0)

    Currently no fix is planned

  • No fix plannedSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA00-7BN0)

    Currently no fix is planned

  • No fix plannedSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA01-7BN0)

    Currently no fix is planned

  • No fix plannedSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA00-4BN0)

    Currently no fix is planned

  • No fix plannedSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA01-4BN0)

    Currently no fix is planned

  • No fix plannedSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU00-4BN0)

    Currently no fix is planned

  • No fix plannedSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU01-4BN0)

    Currently no fix is planned

  • Fixed SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)

    Update to V7.0.3 or later version

  • Fixed SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)

    Update to V7.0.3 or later version

  • Fixed SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)

    Update to V7.0.3 or later version

  • Fixed SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)

    Update to V7.0.3 or later version

  • FixedDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200P

    Update to V4.6 Patch 01 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109781345/
  • FixedSIMATIC CFU PA (6ES7655-5PX11-0XX0)

    Update to V1.2.0 or later version

  • FixedSIMATIC ET 200MP IM 155-5 PN BA (6ES7155-5AA00-0AA0)

    Update to V4.3.0 or later version

  • FixedSIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)

    Update to V4.4.0 or later version

  • FixedSIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47353723/
  • FixedSIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47354354/
  • FixedSIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)

    Update to V1.2.1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109763483/
  • FixedSIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0)

    Update to V4.2.2 or later version

  • FixedSIMATIC ET 200SP IM 155-6 PN HS (6ES7155-6AU00-0DN0)

    Update to V4.0.1 or later version

  • FixedSIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)

    Update to V4.2.2 or later version

  • FixedSIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0)

    Update to V4.2.1 or later version

  • FixedSIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)

    Update to V2.0 or later version

  • FixedSIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47354502/
  • FixedSIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47354578/
  • FixedSIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/62612377/
  • FixedSIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0)

    Update to V4.2.1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109760973/
  • FixedSIMATIC PROFINET Driver

    Update to V2.1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109768047/
  • FixedSIMATIC S7-1200 CPU family (incl. SIPLUS variants)

    Update to V4.4.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109763919/
  • FixedSIMATIC S7-1500 Software Controller

    Update to V2.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109764666/
  • FixedSIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/51466769/
  • FixedSIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40360647/
  • FixedSIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40944925/
  • FixedSIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/85049260/
  • FixedSIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40362228/
  • FixedSIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40945128/
  • FixedSIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/85059804/
  • FixedSIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/85063017/
  • FixedSIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/44442927/
  • FixedSIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/44443101/
  • FixedSIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0)

    Update to V7.0.3 or later version

  • FixedSIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants)

    Update to V6.0.9 or later version

  • FixedSIMATIC S7-410 V8 CPU family (incl. SIPLUS variants)

    Update to V8.2.2 or later version

    https://support.industry.siemens.com/cs/us/en/view/109476571/
  • FixedSIMATIC TDC CP51M1

    Update to V1.1.8 or later version

    https://support.industry.siemens.com/cs/ww/en/view/27049282/
  • FixedSIMATIC TDC CPU555

    Update to V1.1.1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109740119/
  • FixedSIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0)

    Update to V2010 SP3 or later version and apply BIOS and Microsoft Windows updates

    https://support.industry.siemens.com/cs/ww/en/view/109765109/
  • FixedSIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0)

    Update to V2010 SP3 or later version and apply BIOS and Microsoft Windows updates

    https://support.industry.siemens.com/cs/ww/en/view/109765109/
  • FixedSINAMICS DCM

    Update to V1.5 HF1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/44029688/
  • FixedSINAMICS DCP

    Update to V1.3 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109773826/
  • FixedSINAMICS G110M V4.7 PN Control Unit

    Update to V4.7 SP10 HF5 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109756820/
  • FixedSINAMICS G120 V4.7 PN Control Unit (incl. SIPLUS variants)

    Update to V4.7 SP10 HF5 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109756820/
  • FixedSINAMICS G130 V4.7 Control Unit

    Upgrade to V5.2 HF1

    https://support.industry.siemens.com/cs/ww/en/view/109764679/
  • FixedSINAMICS G150 Control Unit

    Upgrade to V5.2 HF1

    https://support.industry.siemens.com/cs/ww/en/view/109764679/
  • FixedSINAMICS GH150 V4.7 Control Unit

    Upgrade to V4.8 SP2 HF9 The update can be obtained from your Siemens representative or via Siemens customer service.

  • FixedSINAMICS GL150 V4.7 Control Unit

    Upgrade to V4.8 SP2 HF9 The update can be obtained from your Siemens representative or via Siemens customer service.

  • FixedSINAMICS GM150 V4.7 Control Unit

    Upgrade to V4.8 SP2 HF9 The update can be obtained from your Siemens representative or via Siemens customer service.

  • FixedSINAMICS S120 V4.7 Control Unit (incl. SIPLUS variants)

    Upgrade to V5.2 HF4

    https://support.industry.siemens.com/cs/ww/en/view/109762626/
  • FixedSINAMICS S150 Control Unit

    Upgrade to V5.2 HF1

    https://support.industry.siemens.com/cs/ww/en/view/109764679/
  • FixedSINAMICS SL150 V4.7 Control Unit

    Update to V4.7 HF33 or later version The update can be obtained from your Siemens representative or via Siemens customer service.

  • FixedSINUMERIK 828D

    Update to V4.8 SP5 or later version The update can be obtained from your Siemens representative or via Siemens customer service.

  • FixedSINUMERIK 840D sl

    Update to V4.8 SP6 or later version The update can be obtained from your Siemens representative or via Siemens customer service.

  • FixedSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)

    Update to V4.4.0 or later version

  • FixedSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)

    Update to V4.4.0 or later version

  • FixedSIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)

    Update to V4.4.0 or later version

  • FixedSIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47353723/
  • FixedSIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47354354/
  • FixedSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0)

    Update to V4.2.2 or later version

  • FixedSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0)

    Update to V4.2.2 or later version

  • FixedSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0)

    Update to V4.2.2 or later version

  • FixedSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0)

    Update to V4.2.2 or later version

  • FixedSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0)

    Update to V4.2.2 or later version

  • FixedSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0)

    Update to V4.2.2 or later version

  • FixedSIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0)

    Update to V4.2.2 or later version

  • FixedSIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0)

    Update to V4.2.1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109760973/
  • FixedSIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0)

    Update to V3.3.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/51466769/
  • FixedSIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40360647/
  • FixedSIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40944925/
  • FixedSIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40362228/
  • FixedSIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40945128/
  • FixedSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)

    Update to V7.0.3 or later version

  • FixedSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)

    Update to V7.0.3 or later version

scry

Advisories like this name the exposed products attackers go after on your perimeter. See what is exposed on your perimeter with a free passive scan.

Free scan