VDE-2020-037

csafDEbeckhoff_psirt

Beckhoff: Privilege Escalation through TwinCat System Tray (TcSysUI.exe)

view advisory published 2020-11-19

The default installation path and its permissions for the TwinCAT runtime allow a local user to replace or modify executables other users of the same system might execute. The issue does not apply for installations underneath C:\Program Files.

01

describes (1)

Related CVEs.

IDseverity exploitable
CVE-2020-12510UShigh7.3OT elevated—
The default installation path of the TwinCAT XAR 3.1 software in all versions is underneath C:\TwinCAT. If the directory does not exist it and further subdirectories are created wi…
02

references

External citations — patches, advisories, analysis.

03

remediations (2)

  • MitigationTwinCAT XAR with default installation path

    Please consider the solution described with the next section (title 'Solution') for new installations only and installations for which it is acceptable to reinstall TwinCAT. For existing installations a script is provided for download at the following link: https://download.beckhoff.com/download/Document/product-security/Advisories/advisory-2020-003/cve-2020-12510.zip external link It changes the permissions of a directory of an already installed TwinCAT 3.1 installation. More precisely, it reads the current permissions of 'C:\Program Files' and copies them to the directory '3.1\System' underneath the installation path of TwinCAT (default 'C:\TwinCAT\3.1\System'). The procedure to use that script is as follows: 1. Download the script, unzip it, and copy it to the IPC. 2. On the IPC log in as administrator and open a PowerShell (Windows-Key + R + 'PowerShell'). 3. At the PowerShell enter the following command to temporarily allow the execution of scripts: set-executionpolicy -ExecutionPolicy Unrestricted -Scope Process (The effect of this is limited to the life-time of the current shell window because of '-Scope Process'.) 4. Then change to the path to where you downloaded the script and execute it: .\cve-2020-12510.ps1 The expected output is 'Copied the permissions from C:\Program Files to \3.1\System'. 5. Close the PowerShell and log out from the IPC as needed. It is safe to apply the script several times. It is safe to run it during full operation of TwinCAT XAR 3.1. There is no need to reboot the IPC afterwards. There is no need to periodically run the script. Future updates of TwinCAT 3.1 will either not touch the permissions which are set by the script or apply more appropriate ones. To apply the procedure to a set of IPCs you can prepare a USB stick with the content of the ZIP file 'cve-2020- 12510.zip' (see download URL above). Then the procedure for each IPC is: 1. Log in as administrator on the IPC. 2. Open the USB stick with the File Explorer (formerly known as Windows Explorer). 3. Double click on the file 'run-cve-2020-12510.bat'. (This simply invokes the PowerShell to execute the script already described above.)

  • FixedTwinCAT XAR with default installation path

    Please consider the mitigation described with the section above for existing installations for operation. Please consider to choose 'C:\Program Files\TwinCAT' during installation of TwinCAT 3.1. If you have installed it already then please uninstall and re-install it with the changed path. Please use the custom installation for this. That will automatically protect the binaries such that they can only be modified by an administrator. Please mind that already installed projects underneath C:\TwinCAT need to be moved. It is recommended to perform a backup of the complete device before such action. For security reasons, please remove the former content of C:\TwinCAT at the end of this sequence. This will also prevent confusion. Update A (25.11.2020): Split into Mitigation and Solution