PPSA-2025-002

csafDEpilz_psirt

Pilz: Missing Authentication in Node-RED integration

view advisory published 2025-07-01

Authentication is not configured by default for the Node-RED server on the Pilz industrial PC IndustrialPI. An unauthenticated remote attacker has full access to the Node-RED server and can run arbitrary operating system commands on the underlying operating system with privileged rights.

01

describes (1)

Related CVEs.

IDseverity exploitable
CVE-2025-41656US—OT elevatedExploit
An unauthenticated remote attacker can run arbitrary commands on the affected devices with high privileges because the authentication for the Node_RED server is not configured by d…
02

references

External citations — patches, advisories, analysis.

03

remediations (2)

  • MitigationFirmware Bullseye <=2024-08 installed on IndustrialPI 4

    Limit network access to the IndustrialPI by using a firewall or similar measures.

  • FixedFirmware Bullseye <=2024-08 installed on IndustrialPI 4

    Consult our PDF with remediations which you can find under [www.pilz.com/downloads](https://www.pilz.com/search#currentPage=1&SEARCH=Security%20Advis.%20IndustrialPI%20Remediat.). In order to activate the authentication as described in the PDF, you have to have the Node-RED service enabled via the web application.

scry

Advisories like this name the exposed products attackers go after on your perimeter. See what is exposed on your perimeter with a free passive scan.