Endress+Hauser: Multiple products prone to multiple vulnerabilities in e!Runtime and CODESYS V3 Runtime
Multiple Endress+Hauser devices are prone to vulnerabilities found in e!Runtime and the CODESYS V3 framework.
describes (16)
Related CVEs.
| ID | severity | exploitable | ||
|---|---|---|---|---|
| CVE-2022-47393US | — | — | ||
An authenticated, remote attacker may use a Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in multiple versions of multiple CODESYS products… | ||||
| CVE-2022-47392US | — | — | ||
An authenticated, remote attacker may use a improper input validation vulnerability in the CmpApp/CmpAppBP/CmpAppForce Components of multiple CODESYS products in multiple versions… | ||||
| CVE-2022-47391US | — | — | ||
In multiple CODESYS products in multiple versions an unauthorized, remote attacker may use a improper input validation vulnerability to read from invalid addresses leading to a den… | ||||
| CVE-2022-47390US | high8.8 | — | ||
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write da… | ||||
| CVE-2022-47389US | — | — | ||
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write da… | ||||
| CVE-2022-47388US | — | — | ||
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write da… | ||||
| CVE-2022-47387US | — | — | ||
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write dat… | ||||
| CVE-2022-47386US | — | — | ||
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write da… | ||||
| CVE-2022-47385US | — | — | ||
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpAppForce Component of multiple CODESYS products in multiple versions to write da… | ||||
| CVE-2022-47384US | — | — | ||
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write dat… | ||||
| CVE-2022-47383US | — | — | ||
An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write da… | ||||
| CVE-2022-47382US | — | — | ||
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in multiple versions to write dat… | ||||
| CVE-2022-47381US | — | — | ||
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into the stack which can le… | ||||
| CVE-2022-47380US | — | — | ||
An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into the stack which can l… | ||||
| CVE-2022-47379US | — | — | ||
An authenticated, remote attacker may use a out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into memory which can lead to a denial… | ||||
| CVE-2022-47378US | medium6.5 | — | ||
Multiple CODESYS products in multiple versions are prone to a improper input validation vulnerability. An authenticated remote attacker may craft specific requests that use the vul… | ||||
references
External citations — patches, advisories, analysis.
- VDE-2026-003: Endress+Hauser: Multiple products prone to multiple vulnerabilities in e!Runtime and CODESYS V3 Runtime - HTMLself
- CERT@VDE Security Advisories for Endress+Hauserexternal
- VDE-2026-003: Endress+Hauser: Multiple products prone to multiple vulnerabilities in e!Runtime and CODESYS V3 Runtime - CSAFself
- Endress+Hauserexternal
remediations (32)
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities. For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.
- Fixed
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected. For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version.