SSA-179516

csafDEsiemens_psirt

SSA-179516 OpenSSL Vulnerability in Industrial Products

view advisory published 2018-08-07

Several Siemens industrial products are affected by a vulnerability in OpenSSL, that could result in data being sent out unencrypted by the SSL/TLS record layer. Siemens has released updates for the affected products and recommends to update to the latest versions.

01

describes (1)

Related CVEs.

IDseverity exploitable
CVE-2017-3737USmedium5.9OT high—
OpenSSL 1.0.2 (starting from version 1.0.2b) introduced an "error state" mechanism. The intent was that if a fatal error occurred during a handshake then OpenSSL would move into th…
02

references

External citations — patches, advisories, analysis.

03

remediations (40)

  • MitigationMindConnect IoT2040

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationMindConnect Nano (IPC227D)

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC HMI WinCC Flexible

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC IPC DiagBase

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC IPC DiagMonitor

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC S7-1200 CPU family (incl. SIPLUS variants)

    Disable web server within the device configuration if it is not used or limit access to the web server on a particular Ethernet/PROFINET port/interface if possible (setting is under General / Web server access).

  • MitigationSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC S7-1500 Software Controller

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC STEP 7 (TIA Portal) V13

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC STEP 7 (TIA Portal) V14

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC STEP 7 (TIA Portal) V15

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC WinCC (TIA Portal) V13

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC WinCC (TIA Portal) V14

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC WinCC (TIA Portal) V15

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC WinCC OA V3.14

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC WinCC OA V3.15

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSIMATIC WinCC OA V3.16

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSINUMERIK Integrate Access MyMachine service engineer client as part of Sinumerik Integrate Product suite

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • MitigationSINUMERIK Integrate Operate Client as part of Sinumerik Integrate Product suite

    Limit network access using appropriate mechanisms (e.g., firewalls)

  • FixedMindConnect IoT2040

    Update to V03.01 or later version

  • FixedMindConnect Nano (IPC227D)

    Update to V03.01 or later version

  • FixedSIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)

    Update to V2.1.6 or later version

    https://support.industry.siemens.com/cs/us/en/view/109759122
  • FixedSIMATIC HMI WinCC Flexible

    Update to V15.1 or later version

    https://support.industry.siemens.com/cs/us/en/view/109758794
  • FixedSIMATIC IPC DiagBase

    Update to V2.1.1.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109792891
  • FixedSIMATIC IPC DiagMonitor

    Update to V5.0.3 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109740915
  • FixedSIMATIC S7-1200 CPU family (incl. SIPLUS variants)

    Update to V4.2.3 or later version

    https://support.industry.siemens.com/cs/us/en/view/109741461
  • FixedSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)

    Update to V2.5.2 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109478459
  • FixedSIMATIC S7-1500 Software Controller

    Update to V2.6 or later version

    https://support.industry.siemens.com/cs/us/en/view/109478528
  • FixedSIMATIC STEP 7 (TIA Portal) V13

    Update to V13 SP2 Update 2 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109759753
  • FixedSIMATIC STEP 7 (TIA Portal) V14

    Update to V14 SP1 Update 6 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109747387
  • FixedSIMATIC STEP 7 (TIA Portal) V15

    Update to V15 Update 2 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109755826
  • FixedSIMATIC WinCC (TIA Portal) V13

    Update to V13 SP2 Update 2 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109759753
  • FixedSIMATIC WinCC (TIA Portal) V14

    Update to V14 SP1 Upd 6 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109747387
  • FixedSIMATIC WinCC (TIA Portal) V15

    Update to V15 Update 2 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109755826
  • FixedSIMATIC WinCC OA V3.14

    Update to V3.14 P021 or later version

    https://www.winccoa.com/downloads/category/versions- patches.html
  • FixedSIMATIC WinCC OA V3.15

    Update to V3.15 P014 or later version

    https://www.winccoa.com/downloads/category/versions- patches.html
  • FixedSIMATIC WinCC OA V3.16

    Update to V3.16 P002 or later version

    https://www.winccoa.com/downloads/category/versions- patches.html
  • FixedSINUMERIK Integrate Access MyMachine service engineer client as part of Sinumerik Integrate Product suite

    Update to V4.1.8, installing latest Sinumerik Integrate Product suite.

  • FixedSINUMERIK Integrate Operate Client as part of Sinumerik Integrate Product suite

    Update to V2.0.12 / 3.0.12, installing latest Sinumerik Integrate Product suite.