ICSA-26-225-05

icsaUScisa_csaf_ot

ANDRITZ HIPASE-250 and 250 SCALA

view advisory published 2026-08-13

Successful exploitation of these vulnerabilities could allow an attacker to read data from the device or gain access to affected workstations.

01

describes (4)

Related CVEs.

IDseverity exploitable
CVE-2026-65313US—OT elevated—
A provisioning script used when installing HIPASE-250 (formerly 250 SCALA) engineering workstations sets a fixed, hard-coded x11vnc password. Because the same credential is applied…
CVE-2026-65311US—OT elevated—
The HTTP server component of ANDRITZ HIPASE-250 (formerly 250 SCALA) in affected versions exposes an undocumented endpoint that changes the server's logging level and target withou…
CVE-2026-65310US—OT elevated—
ANDRITZ HIPASE-250 (formerly 250 SCALA), in the default configuration of affected versions, exposes its data and configuration endpoint without any authentication and permissive CO…
CVE-2026-65309US—OT elevated—
ANDRITZ HIPASE-250 (formerly 250 SCALA) in affected versions stores and transmits user passwords using a reversible format instead of a one-way password hash. This allows an attack…
02

references

External citations — patches, advisories, analysis.

03

remediations (4)

  • FixedHIPASE-250

    ANDRITZ has addressed these issues in version V8.00.00 (released 2024-12) and in version V8.15.00 (released 2026-07) and encourages users to keep their systems updated to the latest version (currently HIPASE-250 Version V8.15.00). For more information, users can contact ANDRITZ at the following website: https://www.andritz.com/group-en/contact

    https://www.andritz.com/group-en/contact
  • FixedHIPASE-250

    ANDRITZ has addressed these issues in version V8.00.00 (released 2024-12) and in version V8.15.00 (released 2026-07) and encourages users to keep their systems updated to the latest version (currently HIPASE-250 Version V8.15.00). For more information, users can contact ANDRITZ at the following website: https://www.andritz.com/group-en/contact

    https://www.andritz.com/group-en/contact
  • FixedHIPASE-250

    ANDRITZ has addressed these issues in version V8.00.00 (released 2024-12) and in version V8.15.00 (released 2026-07) and encourages users to keep their systems updated to the latest version (currently HIPASE-250 Version V8.15.00). For more information, users can contact ANDRITZ at the following website: https://www.andritz.com/group-en/contact

    https://www.andritz.com/group-en/contact
  • FixedHIPASE-250

    ANDRITZ has addressed these issues in version V8.00.00 (released 2024-12) and in version V8.15.00 (released 2026-07) and encourages users to keep their systems updated to the latest version (currently HIPASE-250 Version V8.15.00). For more information, users can contact ANDRITZ at the following website: https://www.andritz.com/group-en/contact

    https://www.andritz.com/group-en/contact