ICSA-26-169-04

icsaUScisa_csaf_ot

Schneider Electric EasyLogic T150 and Saitel DP

view advisory published 2026-05-12

Schneider Electric is aware of a vulnerability in its EasyLogic T150 (formerly known as Saitel DR) and Saitel DP Remote Terminal Unit & Controller products. The [EasyLogic T150 (formerly known as Saitel DR RTU)](https://www.se.com/ww/en/product-country-selector/?pageType=product-range&sourceId=62685#overview) is a field device, offering a solid and powerful modular platform for data acquisition, communication, automation and IED integration for distribution and transmission networks, generation sector and railway. The [Saitel DP RTU](https://www.se.com/ww/en/product-country-selector/?pageType=product-range&sourceId=61747) is a modular platform for medium voltage and high voltage public distribution and transmission substation control. Failure to apply the fix provided below may risk a path traversal–based attack in which an authenticated user could gain unauthorized file access.

01

describes (1)

Related CVEs.

IDseverity exploitable
CVE-2026-6865US——
CWE-22: Improper Limitation of a Pathname to a Restricted Directory (“Path Traversal”) vulnerability that could cause unauthorized access to sensitive files when user-supplied inpu…
02

references

External citations — patches, advisories, analysis.

03

remediations (4)

  • MitigationFirmware Versions 11.06.31 and prior installed on EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • Ensure strict credential controls, even for low privilege users. • Ensure isolation and credentials are in place, as per the product’s security recommendations.

  • MitigationFirmware Versions 11.06.36 and prior installed on Saitel DP Remote Terminal Unit & Controller

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • Ensure strict credential controls, even for low privilege users. • Ensure isolation and credentials are in place, as per the product’s security recommendations.

  • FixedFirmware Versions 11.06.31 and prior installed on EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller

    Version 11.06.32 of EasyLogic T150 (formerly Saitel DR) Remote Terminal Unit & Controller includes a fix for this vulnerability and is available for download here: • Contact Schneider Electric’s Customer Care Center to download this firmware. • Reboot needed: Yes

  • FixedFirmware Versions 11.06.36 and prior installed on Saitel DP Remote Terminal Unit & Controller

    Version 11.06.37 of Saitel DP Remote Terminal Unit & Controller includes a fix for this vulnerability and is available for download here: • Contact Schneider Electric’s Customer Care Center to download this firmware. • Reboot needed: Yes