ICSA-26-169-07

icsaUScisa_csaf_ot

Schneider Electric Easergy, EcoStruxture, PowerLogic, and Saitel Products (Update A)

view advisory published 2026-05-12

Schneider Electric is aware of a vulnerability in the following products: The Easergy C5 is a scalable and interoperable bay controller, protection and merging unit for large and critical infrastructure electrical distribution systems. The Easergy MiCOM P30 is a family of multifunction protection and control relays designed for medium, high and extra high voltage electrical networks. The Easergy MiCOM P40 is a protection relay series for Medium Voltage, High Voltage and Extra High Voltage protection. The Easergy MiCOM C264 is a modular and compact substation or bay controller, smart RTU and MV one box solution The EcoStruxure™ Power Automation System Gateway (EPAS=GTW) is a scalable, interoperable, and rugged communication gateway that helps to remotely monitor and operate electrical processes The EcoStruxure Power Automation System User Interface (EPAS-UI) product is an HMI SCADA designed for electrical networks and substations operations. The EcoStruxure Power Automation System Intelligent Power Management System and Fast Load Shedding (iPMFLS) is a range of solutions designed to overcome size and performances constraints. The EcoStruxure™ Power Operation (EPO) are an on-premises software offers that provides a single platform to monitor and control medium and lower power systems. The PowerLogic™ P5 is a medium voltage protection relay. The PowerLogic™ P7 is a protection and control platform designed for complex and advanced electrical network applications. The PowerLogic™ T300 is a modular platform for medium voltage and low voltage public distribution network management. The PowerLogicTM T500 is a control unit and RTU for substation automation. The Saitel DP RTU is a modular platform for medium voltage and low voltage public distribution and transmission network management. The EasyLogic T150 (formerly Saitel DR RTU) is a field device, offering a solid and powerful platform for data acquisition, communication, automation and IED integration for distribution and transmission networks, generation sector and railway. Failure to apply the fix provided below may risk session hijacking, which could result in malicious actors performing unauthorized operations within the affected system.

01

describes (1)

Related CVEs.

IDseverity exploitable
CVE-2026-4827US——
CWE‑331: Insufficient Entropy vulnerability exists that could lead to unauthorized access when an attacker on the network can exploit weaknesses in session‑management protections.
02

references

External citations — patches, advisories, analysis.

03

remediations (36)

  • MitigationEasergy MiCOM C264

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:• Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions.

  • MitigationEasergy MiCOM C434

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:• Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions.

  • MitigationEasergy MiCOM P138

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:• Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions.

  • MitigationEasergy MiCOM P139

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:• Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions.

  • MitigationEasergy MiCOM P40 Series

    Schneider Electric is establishing a remediation plan for a future version of the Easergy MiCOM P40 Series model numbers with Protocol Option bit as G, H or L. P_ 4_ _ _ _ _ G_ _ _ _ _ M P_ 4_ _ _ _ _ H_ _ _ _ _ M P_ 4_ _ _ _ _ L _ _ _ _ _ M P_ 4_ _ _ _ _ G_ _ _ _ _ L P_ 4_ _ _ _ _ H_ _ _ _ _ L P_ 4_ _ _ _ _ L _ _ _ _ _ L A future version will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: • Ensure P40 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions

  • MitigationEasergy MiCOM P436

    Schneider Electric is establishing a remediation plan for all future versions of the following models of the Easergy MiCOM P30: P437 P532 P631 P634 P436 P438 P638 Future versions will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: • Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions

  • MitigationEasergy MiCOM P437

    Schneider Electric is establishing a remediation plan for all future versions of the following models of the Easergy MiCOM P30: P437 P532 P631 P634 P436 P438 P638 Future versions will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: • Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions

  • MitigationEasergy MiCOM P438

    Schneider Electric is establishing a remediation plan for all future versions of the following models of the Easergy MiCOM P30: P437 P532 P631 P634 P436 P438 P638 Future versions will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: • Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions

  • MitigationEasergy MiCOM P439

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:• Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions.

  • MitigationEasergy MiCOM P532

    Schneider Electric is establishing a remediation plan for all future versions of the following models of the Easergy MiCOM P30: P437 P532 P631 P634 P436 P438 P638 Future versions will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: • Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions

  • MitigationEasergy MiCOM P539

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:• Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions.

  • MitigationEasergy MiCOM P631

    Schneider Electric is establishing a remediation plan for all future versions of the following models of the Easergy MiCOM P30: P437 P532 P631 P634 P436 P438 P638 Future versions will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: • Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions

  • MitigationEasergy MiCOM P632

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:• Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions.

  • MitigationEasergy MiCOM P633

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:• Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions.

  • MitigationEasergy MiCOM P634

    Schneider Electric is establishing a remediation plan for all future versions of the following models of the Easergy MiCOM P30: P437 P532 P631 P634 P436 P438 P638 Future versions will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: • Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions

  • MitigationEasergy MiCOM P638

    Schneider Electric is establishing a remediation plan for all future versions of the following models of the Easergy MiCOM P30: P437 P532 P631 P634 P436 P438 P638 Future versions will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: • Ensure P30 operates within a physically or logically segmented internal network. Access to this network should be tightly controlled using standard security mechanisms such as firewalls, intrusion detection systems (IDS), and other relevant protective measures. • Reduce the “Minimum inactivity period” using the CAE tool to shorten session timeout durations and minimize the risk of unauthorized access due to inactive sessions

  • FixedEasergy C5

    Version 1.1.18 of Easergy C5 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device. Reboot is required

  • FixedEasergy MiCOM C264

    Version D7.34 of MiCOM C264 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device. Reboot is required

  • FixedEasergy MiCOM C434

    Version C434.679.700 Easergy MiCOM C434 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.

  • FixedEasergy MiCOM P138

    Version P138.677.701 Easergy MiCOM P138 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.

  • FixedEasergy MiCOM P139

    Version P139.678.700 Easergy MiCOM P139 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.

  • FixedEasergy MiCOM P439

    Version P439.678.700 Easergy MiCOM P439 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.

  • FixedEasergy MiCOM P539

    Version P539.678.700 Easergy MiCOM P539 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.

  • FixedEasergy MiCOM P632

    Version P632.678.700 Easergy MiCOM P632 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.

  • FixedEasergy MiCOM P633

    Version P633.678.700 Easergy MiCOM P633 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.

  • FixedEasergy MiCOM P634

    Version P634.680.701 Easergy MiCOM P634 includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.

  • FixedEcoStruxure Power Automation System Gateway (EPAS-GTW)

    Version 6.4.610.500.101 of EPAS Gateway includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center to download this software

  • FixedEcoStruxure Power Automation System User Interface (EPAS-UI)

    Version 3.0.4 of EPAS-UI includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center to download this software.

  • FixedEcoStruxure Power Operation

    EPO 2022 CU 7 of EcoStruxure™ Power Operation includes a fix for this vulnerability and is available for download here: • https://community.se.com/t5/EcoStruxure-PowerOperation/Power-Operation-2022-CU7-is-Now-Available/tdp/524787 Reboot needed: yes

    https://community.se.com/t5/EcoStruxure-Power-Operation/Power-Operation-2022-CU7-is-Now-Available/td-p/524787
  • FixedFirmware Version 11.06.30 and prior installed on EasyLogic T150 (formerly Saitel DR)

    HUe Firmware version 11.06.31 includes a fix for this vulnerability and is available for download here: . Contact Schneider Electric’s Customer Care Center to download this software. A reboot is needed to complete the firmware upgrade

  • FixedFirmware version 11.06.36 and prior installed on Saitel DP

    CPU866e Firmware version 11.06.37 includes a fix for this vulnerability and is available for download. Contact Schneider Electric’s Customer Care Center to download this firmware. A reboot is needed to complete the firmware upgrade

  • FixedPowerLogic P5 Protection Relay

    Version V02.503.101 of PowerLogic™ P5 includes a fix for this vulnerability Contact Schneider Electric’s Customer Care Center to download this firmware.

  • FixedPowerLogic P7 Protection and Control Platform

    Version V02.003.001 of PowerLogic™ P7 includes a fix for this vulnerability Contact Schneider Electric’s Customer Care Center to download this firmware.

  • FixedPowerLogic T300

    Version 2.9.5 of PowerLogic™ T300 includes a fix for this vulnerability Contact Schneider Electric’s Customer Care Center to download this firmware. A reboot is needed to complete the firmware upgrade

  • FixedPowerLogic T500

    Version 11.08.03 of PowerLogic™ T500 includes a fix for this vulnerability Contact Schneider Electric’s Customer Care Center to download this firmware. A reboot is needed to complete the firmware upgrade

  • FixediPMFLS

    Version 64.2025.0.14 of iPMFLS includes a fix for this vulnerability. Contact Schneider Electric’s Customer Care Center for information on how to contact your local Application Center to update the device.

scry

Advisories like this name the exposed products attackers go after on your perimeter. See what is exposed on your perimeter with a free passive scan.

Free scan