Schneider Electric SESU
Schneider Electric is aware of a vulnerability in the Schneider Electric Software Update product (also referred to as “SESU”). The main purpose of the SESU software is to notify customers on the availability of hotfixes or new versions to download and install such updates. Failure to apply the fix provided below may risk attacker to write arbitrary data into protected locations, potentially leading to privilege escalation, arbitrary file corruption, exposure of application and system information or a persistent denial of service condition.
describes (1)
Related CVEs.
| ID | severity | exploitable | ||
|---|---|---|---|---|
| CVE-2025-5296US | — | — | ||
CWE-59: Improper Link Resolution Before File Access ('Link Following') vulnerability exists that could cause
arbitrary data to be written to protected locations, potentially leadi… | ||||
references
External citations — patches, advisories, analysis.
- Schneider Electric Software Update - SEVD-2025-224-03 PDF Versionself
- Schneider Electric Software Update - SEVD-2025-224-03 CSAF Versionself
- ICS Advisory ICSA-25-266-03 JSONself
- ICS Advisory ICSA-25-266-03 - Web Versionself
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
remediations (52)
- MitigationSESU
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric BESS ANSI
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric Easergy MiCOM P30
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric Easergy MiCOM P40
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric Easergy Studio
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Architecture Builder
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Automation Device Maintenance
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Automation Expert
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Automation Expert Motion
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Control Expert
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Machine Expert
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Machine Expert Basic
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Machine Expert HVAC
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Microgrid Flex
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Microgrid Operations Medium
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Operator Terminal Expert
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Power Commission Desktop (EPC)
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Power Operations (EPO)
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Process Expert
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Process Expert for AVEVA System Platform
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric Harmony XB5S Soft
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric PowerLogic P5
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric PowerLogic P7
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric SoMove
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric ZelioSoft 2
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- MitigationSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric eXLhoist Configuration Software
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: SESU Installation Directory (chosen by the customer at installation time) should not be accessible from the network and only by trusted persons.
- FixedSESU
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric BESS ANSI
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric Easergy MiCOM P30
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric Easergy MiCOM P40
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric Easergy Studio
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Architecture Builder
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Automation Device Maintenance
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Automation Expert
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Automation Expert Motion
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Control Expert
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Machine Expert
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Machine Expert Basic
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Machine Expert HVAC
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Microgrid Flex
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Microgrid Operations Medium
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Operator Terminal Expert
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Power Commission Desktop (EPC)
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Power Operations (EPO)
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Process Expert
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric EcoStruxure Process Expert for AVEVA System Platform
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric Harmony XB5S Soft
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric PowerLogic P5
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric PowerLogic P7
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric SoMove
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric ZelioSoft 2
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe - FixedSchneider Electric SESU Versions prior to v3.0.12 installed on Schneider Electric eXLhoist Configuration Software
Version 3.0.12 of SESU includes a fix for this vulnerability and is available for download here: https://www.seupdate.schneiderelectric.com/download/SystemConsistency/Soft wareUpdate/SESU_latest_version/SESU_latest _setup_sfx.exe Follow the installation instructions. If a predecessor version of SESU is already installed, then the update to V3.0.12 will be done automatically as a critical update in the background depending on the “automatic” update configuration.
https://www.seupdate.schneider-electric.com/download/SystemConsistency/SoftwareUpdate/SESU_latest_version/SESU_latest_setup_sfx.exe