ICSA-13-295-01

icsaUScisa_csaf_ot

WellinTech KingView ActiveX Vulnerabilities

view advisory published 2013-07-25

This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov

01

describes (2)

Related CVEs.

IDseverity exploitable
CVE-2013-6128USmedium5.8Exploit
The KCHARTXYLib.KChartXY ActiveX control in KChartXY.ocx before 65.30.30000.10002 in WellinTech KingView before 6.53 does not properly restrict SaveToFile method calls, which allow…
CVE-2013-6127USmedium5.8Exploit
The SUPERGRIDLib.SuperGrid ActiveX control in SuperGrid.ocx before 65.30.30000.10002 in WellinTech KingView before 6.53 does not properly restrict ReplaceDBFile method calls, which…
02

references

External citations — patches, advisories, analysis.

03

remediations (2)

  • MitigationKingView

    It is also possible to correct the flaw by implementing the following workarounds: Set the kill-bit on the KChartXY ActiveX Control (CLSID A9A2011A-1E02-4242-AAE0-B239A6F88BAC). Set the kill-bit on the SuperGrid ActiveX Control (CLSID F494550F-A028-4817-A7B5-E5F2DCB4A47E).

  • MitigationKingView

    It is also possible to correct the flaw by implementing the following workarounds: Set the kill-bit on the KChartXY ActiveX Control (CLSID A9A2011A-1E02-4242-AAE0-B239A6F88BAC). Set the kill-bit on the SuperGrid ActiveX Control (CLSID F494550F-A028-4817-A7B5-E5F2DCB4A47E).