ICSA-21-068-06

icsaUScisa_csaf_ot

Siemens TCP/IP Stack Vulnerabilities-AMNESIA:33 in SENTRON PAC / 3VA Devices (Update C)

view advisory published 2021-03-09

Security researchers discovered and disclosed 33 vulnerabilities in several open-source TCP/IP stacks for embedded devices, also known as "AMNESIA:33" vulnerabilities. This advisory describes the impact of two of these vulnerabilities (CVE-2020-13987, CVE-2020-17437) to Siemens products. Siemens has released updates for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where updates are not available. The impact of another "AMNESIA:33" vulnerability (CVE-2020-13988) is described in Siemens Security Advisory SSA-541017.

01

describes (2)

Related CVEs.

IDseverity exploitable
CVE-2020-17437UShigh8.2—
An issue was discovered in uIP 1.0, as used in Contiki 3.0 and other products. When the Urgent flag is set in a TCP packet, and the stack is configured to ignore the urgent data, t…
CVE-2020-13987UShigh7.5—
An issue was discovered in Contiki through 3.0. An Out-of-Bounds Read vulnerability exists in the uIP TCP/IP Stack component when calculating the checksums for IP packets in upper_…
02

references

External citations — patches, advisories, analysis.

03

remediations (24)

  • MitigationSENTRON 3VA COM100/800

    For successful exploitation, an attacking system must be located in the same Modbus TCP segment as a vulnerable device. Therefore ensure that only trusted systems are attached to that segment and only trusted persons have access.

  • MitigationSENTRON 3VA COM100/800

    For successful exploitation, an attacking system must be located in the same Modbus TCP segment as a vulnerable device. Therefore ensure that only trusted systems are attached to that segment and only trusted persons have access.

  • MitigationSENTRON 3VA DSP800

    For successful exploitation, an attacking system must be located in the same Modbus TCP segment as a vulnerable device. Therefore ensure that only trusted systems are attached to that segment and only trusted persons have access.

  • MitigationSENTRON PAC2200 (with CLP Approval)

    For successful exploitation, an attacking system must be located in the same Modbus TCP segment as a vulnerable device. Therefore ensure that only trusted systems are attached to that segment and only trusted persons have access.

  • MitigationSENTRON PAC2200 (with MID Approval)

    For successful exploitation, an attacking system must be located in the same Modbus TCP segment as a vulnerable device. Therefore ensure that only trusted systems are attached to that segment and only trusted persons have access.

  • MitigationSENTRON PAC2200 (without MID Approval)

    For successful exploitation, an attacking system must be located in the same Modbus TCP segment as a vulnerable device. Therefore ensure that only trusted systems are attached to that segment and only trusted persons have access.

  • MitigationSENTRON PAC3200

    For successful exploitation, an attacking system must be located in the same Modbus TCP segment as a vulnerable device. Therefore ensure that only trusted systems are attached to that segment and only trusted persons have access.

  • MitigationSENTRON PAC3200

    For successful exploitation, an attacking system must be located in the same Modbus TCP segment as a vulnerable device. Therefore ensure that only trusted systems are attached to that segment and only trusted persons have access.

  • MitigationSENTRON PAC3200T

    For successful exploitation, an attacking system must be located in the same Modbus TCP segment as a vulnerable device. Therefore ensure that only trusted systems are attached to that segment and only trusted persons have access.

  • MitigationSENTRON PAC3220

    For successful exploitation, an attacking system must be located in the same Modbus TCP segment as a vulnerable device. Therefore ensure that only trusted systems are attached to that segment and only trusted persons have access.

  • MitigationSENTRON PAC4200

    For successful exploitation, an attacking system must be located in the same Modbus TCP segment as a vulnerable device. Therefore ensure that only trusted systems are attached to that segment and only trusted persons have access.

  • MitigationSENTRON PAC4200

    For successful exploitation, an attacking system must be located in the same Modbus TCP segment as a vulnerable device. Therefore ensure that only trusted systems are attached to that segment and only trusted persons have access.

  • No fix plannedSENTRON PAC2200 (with CLP Approval)

    Currently no remediation is planned

  • FixedSENTRON 3VA COM100/800

    Update to V4.4.1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109765343/
  • FixedSENTRON 3VA COM100/800

    Update to V4.4.1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109765343/
  • FixedSENTRON 3VA DSP800

    Update to V4.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109799046/
  • FixedSENTRON PAC2200 (with MID Approval)

    MID-certified devices do not support firmware updates; V3.2.2 is contained in devices that are labeled as "M22 MID"

  • FixedSENTRON PAC2200 (without MID Approval)

    Update to V3.2.2 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109760897/
  • FixedSENTRON PAC3200

    Update to V2.4.7 or later version

    https://support.industry.siemens.com/cs/ww/en/view/31674577/
  • FixedSENTRON PAC3200

    Update to V2.4.7 or later version

    https://support.industry.siemens.com/cs/ww/en/view/31674577/
  • FixedSENTRON PAC3200T

    Update to V3.2.2 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109793060/
  • FixedSENTRON PAC3220

    Update to V3.2.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109780938/
  • FixedSENTRON PAC4200

    Update to V2.3.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/35029840/
  • FixedSENTRON PAC4200

    Update to V2.3.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/35029840/