ICSA-21-152-01

icsaUScisa_csaf_ot

Siemens SIMATIC S7-1200 and S7-1500 CPU Families (Update A)

view advisory published 2021-05-28

SIMATIC S7-1200 and S7-1500 CPU products contain a memory protection bypass vulnerability that could allow an attacker to write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks. Siemens has released updates for several affected products and strongly recommends to update to the latest versions. Siemens recommends specific countermeasures for products where updates are not, or not yet available.

01

describes (1)

Related CVEs.

IDseverity exploitable
CVE-2020-15782UScritical9.8—
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions…
02

references

External citations — patches, advisories, analysis.

03

remediations (14)

  • MitigationSIMATIC Drive Controller family

    Apply "defense in depth" as outlined on pages 12ff of the operational guidelines for Industrial Security, especially: - Plant security: Physical prevention of access to critical components - Network security: Ensure that PLC systems are not connected to untrusted networks * System integrity: Configure, maintain and protect your device by applying applicable compensating controls and using built-in security capabilities

  • MitigationSIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)

    Apply "defense in depth" as outlined on pages 12ff of the operational guidelines for Industrial Security, especially: - Plant security: Physical prevention of access to critical components - Network security: Ensure that PLC systems are not connected to untrusted networks * System integrity: Configure, maintain and protect your device by applying applicable compensating controls and using built-in security capabilities

  • MitigationSIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)

    Apply "defense in depth" as outlined on pages 12ff of the operational guidelines for Industrial Security, especially: - Plant security: Physical prevention of access to critical components - Network security: Ensure that PLC systems are not connected to untrusted networks * System integrity: Configure, maintain and protect your device by applying applicable compensating controls and using built-in security capabilities

  • MitigationSIMATIC S7-1200 CPU family (incl. SIPLUS variants)

    Apply "defense in depth" as outlined on pages 12ff of the operational guidelines for Industrial Security, especially: - Plant security: Physical prevention of access to critical components - Network security: Ensure that PLC systems are not connected to untrusted networks * System integrity: Configure, maintain and protect your device by applying applicable compensating controls and using built-in security capabilities

  • MitigationSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)

    Apply "defense in depth" as outlined on pages 12ff of the operational guidelines for Industrial Security, especially: - Plant security: Physical prevention of access to critical components - Network security: Ensure that PLC systems are not connected to untrusted networks * System integrity: Configure, maintain and protect your device by applying applicable compensating controls and using built-in security capabilities

  • MitigationSIMATIC S7-1500 Software Controller

    Apply "defense in depth" as outlined on pages 12ff of the operational guidelines for Industrial Security, especially: - Plant security: Physical prevention of access to critical components - Network security: Ensure that PLC systems are not connected to untrusted networks * System integrity: Configure, maintain and protect your device by applying applicable compensating controls and using built-in security capabilities

  • MitigationSIMATIC S7-PLCSIM Advanced

    Apply "defense in depth" as outlined on pages 12ff of the operational guidelines for Industrial Security, especially: - Plant security: Physical prevention of access to critical components - Network security: Ensure that PLC systems are not connected to untrusted networks * System integrity: Configure, maintain and protect your device by applying applicable compensating controls and using built-in security capabilities

  • No fix availableSIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)

    Currently no remediation is available

  • FixedSIMATIC Drive Controller family

    Update to V2.9.2 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109773914/
  • FixedSIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)

    Update to V21.9 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109759122/
  • FixedSIMATIC S7-1200 CPU family (incl. SIPLUS variants)

    Update to V4.5.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109793280/
  • FixedSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)

    Update to V2.9.2 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109478459/
  • FixedSIMATIC S7-1500 Software Controller

    Update to V21.9 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109478528/
  • FixedSIMATIC S7-PLCSIM Advanced

    Update to V4.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109795016/
scry

Advisories like this name the exposed products attackers go after on your perimeter. See what is exposed on your perimeter with a free passive scan.

Free scan