ICSA-24-331-04

icsaUScisa_csaf_ot

Hitachi Energy MicroSCADA Pro/X SYS600 (Update A)

view advisory published 2024-08-27

Hitachi Energy is aware of the multiple vulnerabilities that affect the MicroSCADA Pro/X SYS600 product versions listed in this document. An attacker successfully exploiting these vulnerabilities can cause confidentiality, integrity and availability impacts. Please refer to the Recommended Immediate Actions for information about the mitigation/remediation.

01

describes (5)

Related CVEs.

IDseverity exploitable
CVE-2024-7941USmedium4.3—
An HTTP parameter may contain a URL value and could cause the web application to redirect the request to the specified URL. By modifying the URL value to a malicious site, an attac…
CVE-2024-7940UScritical9.8OT elevated—
The product exposes a service that is intended for local only to all network interfaces without any authentication.
CVE-2024-4872UShigh8.8—
A vulnerability exists in the query validation of the MicroSCADA Pro/X SYS600 product. If exploited this could allow an authenticated attacker to inject code towards persistent dat…
CVE-2024-3982UShigh8.2OT elevated—
An attacker with local access to machine where MicroSCADA X SYS600 is installed, could enable the session logging supporting the product and try to exploit a session hijacking of a…
CVE-2024-3980UShigh8.8—
The MicroSCADA Pro/X SYS600 product allows an authenticated user input to control or influence paths or file names that are used in filesystem operations. If exploited the vulnerab…
02

references

External citations — patches, advisories, analysis.

03

remediations (10)

  • MitigationMicroSCADA Pro/X SYS600

    Follow the mitigation strategy as described in the Mitigation Factors/Workarounds section

  • MitigationMicroSCADA Pro/X SYS600

    Follow the mitigation strategy as described in the Mitigation Factors/Workarounds section

  • MitigationMicroSCADA Pro/X SYS600

    Follow the mitigation strategy as described in the Mitigation Factors/Workarounds section

  • MitigationMicroSCADA Pro/X SYS600

    Follow the mitigation strategy as described in the Mitigation Factors/Workarounds section

  • MitigationMicroSCADA Pro/X SYS600

    Follow the mitigation strategy as described in the Mitigation Factors/Workarounds section

  • FixedMicroSCADA Pro/X SYS600

    Apply the patch 9.4 FP2 HF6 (Installation of previous FP2 hotfixes are required prior to the installation of HF6)

  • FixedMicroSCADA Pro/X SYS600

    Apply the patch 9.4 FP2 HF6 (Installation of previous FP2 hotfixes are required prior to the installation of HF6)

  • FixedMicroSCADA Pro/X SYS600

    Update to version 10.3 vulnerability patch 2025_01 or Update to version 10.6

  • FixedMicroSCADA Pro/X SYS600

    Update to version 10.3 vulnerability patch 2025_01 or Update to version 10.6

  • FixedMicroSCADA Pro/X SYS600

    Update to version 10.5 vulnerability patch 2025_01 or Update to version 10.6