ICSA-24-284-20

icsaUScisa_csaf_ot

Rockwell Automation ControlLogix

view advisory published 2024-10-10

Successful exploitation of this vulnerability could allow an attacker to send a specially crafted CIP message and cause a denial-of-service condition on the affected device.

01

describes (1)

Related CVEs.

IDseverity exploitable
CVE-2024-6207UShigh7.5—
CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html  and send a specially crafted CIP message to the device. If exploited…
02

references

External citations — patches, advisories, analysis.

03

remediations (8)

  • MitigationCompact GuardLogix 5380 SIL 2

    Rockwell Automations recommends users update to V33.017, V34.014, V35.013, or V36.011.

  • MitigationCompact GuardLogix 5380 SIL 3

    Rockwell Automations recommends users update to V33.017, V34.014, V35.013, or V36.011.

  • MitigationCompactLogix 5380

    Rockwell Automations recommends users update to V33.017, V34.014, V35.013, or V36.011.

  • MitigationCompactLogix 5480

    Rockwell Automations recommends users update to V33.017, V34.014, V35.013, or V36.011.

  • MitigationControlLogix 5580

    Rockwell Automations recommends users update to V33.017, V34.014, V35.013, or V36.011.

  • MitigationControlLogix 5580 Process

    Rockwell Automations recommends users update to V33.017, V34.014, V35.013, or V36.011.

  • MitigationFactoryTalk Logix Echo

    Rockwell Automations recommends users update to V33.017, V34.014, V35.013, or V36.011.

  • MitigationGuardLogix 5580

    Rockwell Automations recommends users update to V33.017, V34.014, V35.013, or V36.011.