Siemens SICAM Q100 Devices
The web server of SICAM Q100 devices, versions before V2.60, contains a Cross Site Request Forgery (CSRF) vulnerability and is missing cookie protection flags. This could allow an attacker to perform arbitrary actions on the device on behalf of a legitimate user, or impersonate that user. Siemens has released new versions for the affected products and recommends to update to the latest versions.
describes (2)
Related CVEs.
| ID | severity | exploitable | ||
|---|---|---|---|---|
| CVE-2023-31238US | medium4.8 | — | ||
A vulnerability has been identified in SICAM P850 (7KG8500-0AA00-0AA0) (All versions < V3.11), SICAM P850 (7KG8500-0AA00-2AA0) (All versions < V3.11), SICAM P850 (7KG8500-0AA10-0AA… | ||||
| CVE-2023-30901US | high8.8 | — | ||
A vulnerability has been identified in SICAM P850 (7KG8500-0AA00-0AA0) (All versions < V3.11), SICAM P850 (7KG8500-0AA00-2AA0) (All versions < V3.11), SICAM P850 (7KG8500-0AA10-0AA… | ||||
references
External citations — patches, advisories, analysis.
- SSA-480095: Vulnerabilities in the Web Interface of SICAM Q100 Devices before V2.60 - CSAF Versionself
- SSA-480095: Vulnerabilities in the Web Interface of SICAM Q100 Devices before V2.60 - HTML Versionself
- SSA-480095: Vulnerabilities in the Web Interface of SICAM Q100 Devices before V2.60 - PDF Versionself
- SSA-480095: Vulnerabilities in the Web Interface of SICAM Q100 Devices before V2.60 - TXT Versionself
- ICS Advisory ICSA-23-348-13 JSONself
- Recommended Practicesexternal
- ICS Advisory ICSA-23-348-13 - Web Versionself
- Recommended Practicesexternal
remediations (16)
- MitigationPOWER METER SICAM Q100 (7KG9501-0AA01-0AA1)
CVE-2023-30901: Do not access links from untrusted sources while logged in at affected devices
- MitigationPOWER METER SICAM Q100 (7KG9501-0AA01-2AA1)
CVE-2023-30901: Do not access links from untrusted sources while logged in at affected devices
- MitigationPOWER METER SICAM Q100 (7KG9501-0AA31-0AA1)
CVE-2023-30901: Do not access links from untrusted sources while logged in at affected devices
- MitigationPOWER METER SICAM Q100 (7KG9501-0AA31-2AA1)
CVE-2023-30901: Do not access links from untrusted sources while logged in at affected devices
- FixedPOWER METER SICAM Q100 (7KG9501-0AA01-0AA1)
Update to V2.60 or later version
- FixedPOWER METER SICAM Q100 (7KG9501-0AA01-0AA1)
Update to V2.60 or later version
- FixedPOWER METER SICAM Q100 (7KG9501-0AA01-2AA1)
Update to V2.60 or later version
- FixedPOWER METER SICAM Q100 (7KG9501-0AA01-2AA1)
Update to V2.60 or later version
- FixedPOWER METER SICAM Q100 (7KG9501-0AA31-0AA1)
Update to V2.60 or later version
- FixedPOWER METER SICAM Q100 (7KG9501-0AA31-0AA1)
Update to V2.60 or later version
- FixedPOWER METER SICAM Q100 (7KG9501-0AA31-2AA1)
Update to V2.60 or later version
- FixedPOWER METER SICAM Q100 (7KG9501-0AA31-2AA1)
Update to V2.60 or later version
- WorkaroundPOWER METER SICAM Q100 (7KG9501-0AA01-0AA1)
CVE-2023-31238: Restrict access to port 443/tcp to trusted IP addresses only
- WorkaroundPOWER METER SICAM Q100 (7KG9501-0AA01-2AA1)
CVE-2023-31238: Restrict access to port 443/tcp to trusted IP addresses only
- WorkaroundPOWER METER SICAM Q100 (7KG9501-0AA31-0AA1)
CVE-2023-31238: Restrict access to port 443/tcp to trusted IP addresses only
- WorkaroundPOWER METER SICAM Q100 (7KG9501-0AA31-2AA1)
CVE-2023-31238: Restrict access to port 443/tcp to trusted IP addresses only