ICSA-24-011-08

icsaUScisa_csaf_ot

Siemens SICAM A8000

view advisory published 2024-01-09

The CPCI85 firmware of SICAM A8000 CP-8031 and CP-8050 is affected by a command injection vulnerability that could allow an authenticated remote attacker to inject commands that are executed on the device with root privileges during device startup. Siemens has released new versions for the affected products and recommends to update to the latest versions.

01

describes (1)

Related CVEs.

IDseverity exploitable
CVE-2023-42797UShigh7.2—
A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05.20), CP-8050 MASTER MODULE (All versions < CPCI85 V05.20). The network configuration service…
02

references

External citations — patches, advisories, analysis.

03

remediations (4)

  • MitigationCP-8031 MASTER MODULE (6MF2803-1AA00)

    Review the list of users that are allowed to modify the network configuration and apply strong passwords

  • MitigationCP-8050 MASTER MODULE (6MF2805-0AA00)

    Review the list of users that are allowed to modify the network configuration and apply strong passwords

  • FixedCP-8031 MASTER MODULE (6MF2803-1AA00)

    Update to CPCI85 V05.20 or later version

  • FixedCP-8050 MASTER MODULE (6MF2805-0AA00)

    Update to CPCI85 V05.20 or later version