ICSA-23-012-10

icsaUScisa_csaf_ot

Siemens Automation License Manager

view advisory published 2023-01-10

Siemens Automation License Manager contains two vulnerabilities which, when combined, could allow an attacker to modify and rename license files, extract licenses and overwrite arbitrary files on the target system potentially leading to privilege escalation and remote code execution. The affected functionality is not available for remote attackers in the default configuration since version V6.0 SP2 of Automation License Manager. Siemens has released an update for Automation License Manager V6 and recommends to update to the latest version. Siemens recommends specific countermeasures for products where updates are not, or not yet available.

01

describes (2)

Related CVEs.

IDseverity exploitable
CVE-2022-43514UScritical9.8—
A vulnerability has been identified in Automation License Manager V5 (All versions), Automation License Manager V6 (All versions < V6.0 SP9 Upd4), TeleControl Server Basic V3 (All…
CVE-2022-43513UShigh7.5—
A vulnerability has been identified in Automation License Manager V5 (All versions), Automation License Manager V6 (All versions < V6.0 SP9 Upd4), TeleControl Server Basic V3 (All…
02

references

External citations — patches, advisories, analysis.

03

remediations (12)

  • MitigationAutomation License Manager V5

    If no remote connections are needed, disable “Allow Remote Connections” on the Automation License Manager settings menu (default since version V6.0 SP2)

  • MitigationAutomation License Manager V5

    If no remote connections are needed, disable “Allow Remote Connections” on the Automation License Manager settings menu (default since version V6.0 SP2)

  • MitigationAutomation License Manager V6

    If no remote connections are needed, disable “Allow Remote Connections” on the Automation License Manager settings menu (default since version V6.0 SP2)

  • MitigationAutomation License Manager V6

    If no remote connections are needed, disable “Allow Remote Connections” on the Automation License Manager settings menu (default since version V6.0 SP2)

  • No fix plannedAutomation License Manager V5

    Currently no fix is planned

  • No fix plannedAutomation License Manager V5

    Currently no fix is planned

  • FixedAutomation License Manager V6

    Update to V6.0 SP9 Upd4 or later version

    https://support.industry.siemens.com/cs/ww/en/view/114358/
  • FixedAutomation License Manager V6

    Update to V6.0 SP9 Upd4 or later version

    https://support.industry.siemens.com/cs/ww/en/view/114358/
  • WorkaroundAutomation License Manager V5

    If remote connections are needed, limit remote access to port 4410/tcp to trusted systems only

  • WorkaroundAutomation License Manager V5

    If remote connections are needed, limit remote access to port 4410/tcp to trusted systems only

  • WorkaroundAutomation License Manager V6

    If remote connections are needed, limit remote access to port 4410/tcp to trusted systems only

  • WorkaroundAutomation License Manager V6

    If remote connections are needed, limit remote access to port 4410/tcp to trusted systems only