Mitsubishi Electric MELSEC iQ-R Series C Controller Module (Update B)
view advisory published 2021-10-07
Successful exploitation of this vulnerability could prevent the module from starting up. If successfully exploited, a system reset would be required for recovery.
01
describes (1)
Related CVEs.
| ID | severity | exploitable | ||
|---|---|---|---|---|
| CVE-2021-20600US | medium5.9 | — | ||
Uncontrolled resource consumption in Mitsubishi Electric MELSEC iQ-R series C Controller Module R12CCPU-V Firmware Versions "16" and prior allows a remote unauthenticated attacker… | ||||
02
references
External citations — patches, advisories, analysis.
03
remediations (1)
- MitigationR12CCPU-V
If a System WDT error occurs at start up, there is a possibility the C Controller Module has been attacked. In this case, disconnect the LAN cable of the module and restart. After confirming the module has started normally, make a LAN connection.