Siemens SIPROTEC 5 and DIGSI 5 (Update C)
Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design. Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment. Recommended security guidelines to Digital Grid Products can be found at:
describes (2)
Related CVEs.
| ID | severity | exploitable | ||
|---|---|---|---|---|
| CVE-2019-10931US | high7.5 | — | ||
A vulnerability has been identified in All other SIPROTEC 5 device types with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions ), DIGSI… | ||||
| CVE-2019-10930US | high7.5 | — | ||
A vulnerability has been identified in All other SIPROTEC 5 device types with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions ), DIGSI… | ||||
references
External citations — patches, advisories, analysis.
- SSA-899560: Vulnerabilities in SIPROTEC 5 relays and DIGSI 5 - HTML Versionself
- ICS Advisory ICSA-19-190-05 JSONself
- Recommended Practicesexternal
- ICS Advisory ICSA-19-190-05 - Web Versionself
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
remediations (17)
- MitigationAll other SIPROTEC 5 device types with CPU variants CP300 and CP100 and the respective Ethernet communication modules
Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)
- MitigationAll other SIPROTEC 5 device types with CPU variants CP300 and CP100 and the respective Ethernet communication modules
Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)
- MitigationDIGSI 5 engineering software
Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)
- MitigationDIGSI 5 engineering software
Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)
- MitigationSIPROTEC 5 device types 6MD85, 6MD86, 6MD89, 7UM85, 7SA87, 7SD87, 7SL87, 7VK87, 7SA82, 7SA86, 7SD82, 7SD86, 7SL82, 7SL86, 7SJ86, 7SK82, 7SK85, 7SJ82, 7SJ85, 7UT82, 7UT85, 7UT86, 7UT87 and 7VE85 with CPU variants CP300 and CP100 and the respective Ethernet communication modules
Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)
- MitigationSIPROTEC 5 device types 6MD85, 6MD86, 6MD89, 7UM85, 7SA87, 7SD87, 7SL87, 7VK87, 7SA82, 7SA86, 7SD82, 7SD86, 7SL82, 7SL86, 7SJ86, 7SK82, 7SK85, 7SJ82, 7SJ85, 7UT82, 7UT85, 7UT86, 7UT87 and 7VE85 with CPU variants CP300 and CP100 and the respective Ethernet communication modules
Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)
- MitigationSIPROTEC 5 device types 7SS85 and 7KE85
Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)
- MitigationSIPROTEC 5 device types 7SS85 and 7KE85
Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)
- MitigationSIPROTEC 5 device types with CPU variants CP200 and the respective Ethernet communication modules
Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)
- MitigationSIPROTEC 5 device types with CPU variants CP200 and the respective Ethernet communication modules
Activate role based access control (RBAC) in the device (supported in SIPROTEC 5 firmware versions V7.80 and higher)
- FixedDIGSI 5 engineering software
Update to V7.90 or later version and activate the client authorization feature https://support.industry.siemens.com/cs/us/en/view/109767686
- FixedDIGSI 5 engineering software
Update to V7.90 or later version and activate the client authorization feature https://support.industry.siemens.com/cs/us/en/view/109767686
- FixedSIPROTEC 5 device types 6MD85, 6MD86, 6MD89, 7UM85, 7SA87, 7SD87, 7SL87, 7VK87, 7SA82, 7SA86, 7SD82, 7SD86, 7SL82, 7SL86, 7SJ86, 7SK82, 7SK85, 7SJ82, 7SJ85, 7UT82, 7UT85, 7UT86, 7UT87 and 7VE85 with CPU variants CP300 and CP100 and the respective Ethernet communication modules
Update to V7.90 or later version. Search for "SIPROTEC 5 - DIGSI Device Drivers" on the Siemens Industry Online Support site. The latest firmware version for the communication modules can also be found on each device specific download page. Applying the update causes the device / module to go through a single restart cycle. https://support.industry.siemens.com/cs/ww/en/
- FixedSIPROTEC 5 device types 6MD85, 6MD86, 6MD89, 7UM85, 7SA87, 7SD87, 7SL87, 7VK87, 7SA82, 7SA86, 7SD82, 7SD86, 7SL82, 7SL86, 7SJ86, 7SK82, 7SK85, 7SJ82, 7SJ85, 7UT82, 7UT85, 7UT86, 7UT87 and 7VE85 with CPU variants CP300 and CP100 and the respective Ethernet communication modules
Update to V7.90 or later version. Search for "SIPROTEC 5 - DIGSI Device Drivers" on the Siemens Industry Online Support site. The latest firmware version for the communication modules can also be found on each device specific download page. Applying the update causes the device / module to go through a single restart cycle. https://support.industry.siemens.com/cs/ww/en/
- FixedSIPROTEC 5 device types 7SS85 and 7KE85
Update to V8.01 or later version. Search for "SIPROTEC 5 - DIGSI Device Drivers" on the Siemens Industry Online Support site. Applying the update causes the device / module to go through a single restart cycle. https://support.industry.siemens.com/cs/ww/en/
- FixedSIPROTEC 5 device types 7SS85 and 7KE85
Update to V8.01 or later version. Search for "SIPROTEC 5 - DIGSI Device Drivers" on the Siemens Industry Online Support site. Applying the update causes the device / module to go through a single restart cycle. https://support.industry.siemens.com/cs/ww/en/
- FixedSIPROTEC 5 device types with CPU variants CP200 and the respective Ethernet communication modules
Update to V7.59 or later version. Search for "SIPROTEC 5 - DIGSI Device Drivers" on the Siemens Industry Online Support site. The latest firmware version for the communication modules can also be found on each device specific download page. Applying the update causes the device / module to go through a single restart cycle. https://support.industry.siemens.com/cs/ww/en/
https://support.industry.siemens.com/cs/ww/en/
Advisories like this name the exposed products attackers go after on your perimeter. See what is exposed on your perimeter with a free passive scan.