ICSA-20-112-01

icsaUScisa_csaf_ot

Inductive Automation Ignition

view advisory published 2020-04-21

Successful exploitation of this vulnerability could allow an attacker to write endless log statements into the database, which could result in a denial-of-service condition.

01

describes (1)

Related CVEs.

IDseverity exploitable
CVE-2020-10641UShigh7.5OT elevated—
An unprotected logging route may allow an attacker to write endless log statements into the database without space limits or authentication. This results in consuming the entire av…
02

references

External citations — patches, advisories, analysis.

03

remediations (2)

  • MitigationIgnition 8 Gateway

    For gateways that are deployed behind a web application firewall or reverse proxy, deploy a rule to deny access to all gateway HTTP requests that include the path: /data/perspective/print-to-log.

  • FixedIgnition 8 Gateway

    Upgrade Ignition 8 Gateway to v8.0.10

    https://inductiveautomation.com/downloads/
scry

Advisories like this name the exposed products attackers go after on your perimeter. See what is exposed on your perimeter with a free passive scan.

Free scan