ICSA-19-043-05

icsaUScisa_csaf_ot

Siemens Intel Active Management Technology of SIMATIC IPCs

view advisory published 2019-02-12

As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.

01

describes (3)

Related CVEs.

IDseverity exploitable
CVE-2018-3658USmedium5.3—
Multiple memory leaks in Intel AMT in Intel CSME firmware versions before 12.0.5 may allow an unauthenticated user with Intel AMT provisioned to potentially cause a partial denial…
CVE-2018-3657USmedium6.7—
Multiple buffer overflows in Intel AMT in Intel CSME firmware versions before version 12.0.5 may allow a privileged user to potentially execute arbitrary code with Intel AMT execut…
CVE-2018-3616USmedium5.9OT elevated—
Bleichenbacher-style side channel vulnerability in TLS implementation in Intel Active Management Technology before 12.0.5 may allow an unauthenticated user to potentially obtain th…
02

references

External citations — patches, advisories, analysis.

03

remediations (66)

  • MitigationSIMATIC FieldPG M5

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC FieldPG M5

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC FieldPG M5

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC427E (incl. SIPLUS variants)

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC427E (incl. SIPLUS variants)

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC427E (incl. SIPLUS variants)

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC477E

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC477E

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC477E

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC547E

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC547E

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC547E

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC547G

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC547G

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC547G

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC627D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC627D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC627D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC647D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC647D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC647D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC677D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC677D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC677D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC827D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC827D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC827D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC847D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC847D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC IPC847D

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC ITP1000

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC ITP1000

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • MitigationSIMATIC ITP1000

    As a prerequisite for an attack, an attacker must be able to run malicious code on affected systems. Therefore, Siemens recommends determining if it is possible that untrusted code can be run on these systems, or if existing measures implemented by the operator reduce the likelihood of untrusted code being run.

  • FixedSIMATIC FieldPG M5

    Update to V22.01.06 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC FieldPG M5

    Update to V22.01.06 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC FieldPG M5

    Update to V22.01.06 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC427E (incl. SIPLUS variants)

    Update to V21.01.09 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC427E (incl. SIPLUS variants)

    Update to V21.01.09 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC427E (incl. SIPLUS variants)

    Update to V21.01.09 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC477E

    Update to V21.01.09 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC477E

    Update to V21.01.09 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC477E

    Update to V21.01.09 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC547E

    Update to R1.30.0 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC547E

    Update to R1.30.0 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC547E

    Update to R1.30.0 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC547G

    Update to R1.23.0 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC547G

    Update to R1.23.0 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC547G

    Update to R1.23.0 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC627D

    Update to V19.02.11 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC627D

    Update to V19.02.11 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC627D

    Update to V19.02.11 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC647D

    Update to V19.01.14 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC647D

    Update to V19.01.14 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC647D

    Update to V19.01.14 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC677D

    Update to V19.02.11 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC677D

    Update to V19.02.11 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC677D

    Update to V19.02.11 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC827D

    Update to V19.02.11 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC827D

    Update to V19.02.11 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC827D

    Update to V19.02.11 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC847D

    Update to V19.01.14 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC847D

    Update to V19.01.14 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC IPC847D

    Update to V19.01.14 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC ITP1000

    Update to V23.01.04 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC ITP1000

    Update to V23.01.04 https://support.industry.siemens.com/cs/us/en/view/109747626

  • FixedSIMATIC ITP1000

    Update to V23.01.04 https://support.industry.siemens.com/cs/us/en/view/109747626